Your Cart (0)
Your cart is empty
Tax included and shipping calculated at checkout
Connect with our team or quickly find hydronic product and order information.
Drawer menu
Tax included and shipping calculated at checkout
The right pre-assembled hydronic heating panel must match the number of heating zones, required water flow, connected heat source and piping layout of the system.
Choosing a pre-assembled panel is easier when you start with the system design instead of the panel size or price. The correct panel must coordinate with the heating zones, tubing loops, water flow, pressure loss, heat source and controls used throughout the building.
A pre-assembled panel brings many of the primary circulation, control, air-management and service components together in one organized layout. This can reduce on-site assembly and create a cleaner mechanical installation, but the panel still needs to be matched to a properly designed hydronic system.
A zone is an area controlled by its own thermostat. One zone can contain several PEX tubing loops connected to a manifold.
A loop is an individual tubing circuit. Loop count affects flow requirements, but it does not determine the number of thermostat-controlled zones.
A thermostat controls a heating zone. That zone may contain one or several PEX loops connected to its manifold.
Work through these decisions in order before selecting a product configuration.
Count the areas that need independent thermostat control. Zones are commonly separated by floor, room group, occupancy schedule, desired temperature, type of heat emitter or application. A small garage may need one zone, while a larger home or building may need several independently controlled zones.
Count independently controlled areas first, then determine how many loops and how much flow each zone requires. Do not use the total number of PEX loops as the zone count.
A pump-zoned panel uses a dedicated circulator for each zone. A valve-zoned panel typically uses one system circulator with individual zone valves. Both approaches can provide effective temperature control when they are correctly sized and coordinated with the system piping.
Pump zoning is often considered when zones have different flow requirements or independent circulation is preferred. Valve zoning may fit systems with moderate, relatively similar zone requirements and a design intended to use a shared circulator.
Most pump-zone and valve-zone control panels connect to a separately selected boiler or compatible hydronic heat source. The heat source must be sized for the building's calculated heat loss and designed for the required water temperature and flow.
If the project needs a complete electric solution, an electric boiler panel can combine the boiler, hydronic components and manifold on one assembly. This configuration may suit a garage, addition, remodel or standalone radiant heating application where electric heat is appropriate.
For pump-zoned panels, zone count and pump size are separate decisions. A four-zone panel does not automatically need high-flow pumps, and a one-zone panel is not automatically a low-flow system.
Select the circulator from the required gallons per minute and calculated pumping head of the connected circuit. Tubing size, loop length, manifolds, valves, heat exchangers and glycol concentration can all affect the result.
Pre-assembled panels can support radiant floors, hydronic baseboard, radiators, snow-melting systems, garages, workshops and other closed-loop heating applications. The application affects water temperature, flow, controls and fluid selection.
A system serving different heat emitters may require mixing controls, separate water temperatures or hydraulic separation. Confirm these requirements before choosing a panel configuration.
Compare the exact panel specifications with the piping and electrical plan. Verify boiler supply and return sizes, zone or manifold connections, voltage, thermostat compatibility, fluid requirements, mounting space and service clearances.
Also confirm what is included. Depending on the configuration, the boiler, thermostats, PEX manifolds, distribution tubing and heating loops may be sold separately.
The best configuration depends on how the zones are controlled and whether the project needs an integrated heat source.
Uses one circulator pump per zone and connects to a separately selected boiler or compatible heat source.
Uses one system circulator with individual zone valves and connects to a separate heat source.
Combines an electric boiler with hydronic components and a manifold in one organized assembly.
Matches circulator capacity to the calculated flow and pumping head required by each connected zone.
Confirm wall space, piping connections and service clearances before ordering. Component layout varies by panel configuration.
Warming Systems pump-zone panels are available with standard-flow and high-flow circulator options. Use the figures below as selection guidelines, then verify the final pump against the completed system calculations.
The Grundfos UPS15-58FC configuration provides a listed range of 0 to 17 GPM and 0 to 19 feet of head. Current Warming Systems guidance allows up to eight properly designed 1/2-inch PEX loops per zone, with loop lengths up to 300 feet and approximately 1 GPM per loop.
The Grundfos UPS26-99FC configuration provides a listed range of 0 to 33 GPM and 0 to 29 feet of head. Current Warming Systems guidance allows up to 23 properly designed 1/2-inch PEX loops per zone under the stated design conditions.
Loop quantities are general guidelines, not a substitute for circulator sizing. Final selection must account for required flow, total equivalent piping length, tubing diameter, individual loop lengths, component pressure loss, fluid concentration, water temperature and simultaneous zone operation.
Review the specifications for the exact panel and product variant instead of assuming that every model uses the same connections or components.
The connected boiler may have an internal circulator, or the design may require a separate boiler-loop pump. This boiler-side circulation must be addressed as part of the completed system, even when the heating-zone panel is pre-assembled.
A pre-assembled panel reduces field assembly, but it may not include every part required for a complete heating system.
Confirm the included circulator pump or pumps, zone controller, relay controls and zone valves for the selected configuration.
Check for the expansion tank, air separator, automatic water-feed valve, backflow preventer and pressure gauge.
Verify fill, purge and drain connections, isolation valves, temperature gauges and other service points.
Standard pump-zone and valve-zone panels usually require a separate boiler. Electric boiler panels include the electric heat source.
Confirm whether the PEX manifold, distribution tubing, actuators and heating loops are included or ordered separately.
Identify the piping, electrical, thermostat and control connections that still need to be completed at the job site.
Having these details ready makes it easier to compare panel configurations and resolve design questions before installation begins.
Floor area does not determine the building's heat loss, required water flow or pumping head.
A zone is controlled by a thermostat. One zone can contain multiple individual tubing loops.
The circulator must deliver the required flow against the resistance of the connected circuit.
Pump-zone and valve-zone panels generally connect to a separately selected hydronic heat source.
The completed design may need an internal boiler circulator or a separate boiler-loop pump.
Connection sizes can vary by panel type, pump capacity and exact product configuration.
Two buildings with the same square footage can require different panels because of climate, insulation, ceiling height, windows, floor construction, heat emitters and intended room temperatures. A coordinated design determines the heating load, water temperature, loop layout, required flow and circulator head before equipment is selected.
Warming Systems Hydronic provides hydronic system design services, including heat-load calculations, PEX piping layouts and control-panel design.
The correct number depends on how many areas need independent temperature control. Different floors, room groups, occupancy schedules, applications or heat emitters may justify separate zones.
No. A heating zone is controlled by a thermostat, while a manifold loop is an individual tubing circuit. A single zone may contain several loops.
Pump-zoned panels provide a dedicated circulator for each zone. Valve-zoned panels use individual zone valves with a shared system circulator. The correct choice depends on required flow, pressure loss, zone diversity, piping and the overall control strategy.
A high-flow pump may be appropriate when a zone requires more flow or pumping head than the standard circulator can provide. Make the choice from calculated flow and pressure loss, not only the number of loops.
Not always. Standard pump-zone and valve-zone panels generally connect to a separate heat source. An electric boiler panel is an integrated configuration that includes the electric boiler. Review the exact product listing before ordering.
Pre-assembled panels can be used with several types of hydronic heat distribution. Systems using different water temperatures may require additional mixing, controls or hydraulic separation as part of the overall design.